Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | 6AV6644-0AA01-2AX0 |
| Manufacturer | Siemens AG |
| Product Type | Multi Panel HMI / 12″ Touch Operator Interface |
| Series | SIMATIC MP 377 |
| Display Type | TFT color, 65,536 colors |
| Screen Size | 12.1″ diagonal (246 × 184.5 mm viewable) |
| Resolution | 800 × 600 pixels (SVGA) |
| Touch Technology | Analog resistive (USB mouse/keyboard/barcode supported) |
| Operating System | Windows CE 5.0 |
| User Memory | 12,288 KB Flash/RAM + 12,288 KB option memory |
| Supply Voltage | 24 V DC (20.4 – 28.8 V range) |
| Rated Current | 1.5 A |
| Power Consumption | ~36 W |
| Interfaces | 1× RS422, 1× RS485, 2× Ethernet RJ45 (PROFINET), 2× USB host, 1× CF slot, 1× MMC/SD slot (≤128 MB) |
| Supported Protocols | PROFINET IO, PROFIBUS DP, MPI, TCP/IP, EtherNet/IP, Modbus (RTU/TCP), Sm@rtServer |
| Real-Time Clock | Hardware RTC, battery-backed, synchronizable |
| Front / Rear Protection | IP65 / NEMA 4 / NEMA 12 (front, installed) ; IP20 (rear) |
| Operating Temperature | 0 °C to +50 °C (max ±35° tilt without forced ventilation) |
| Storage Temperature | –20 °C to +60 °C |
| Humidity | ≤85 % RH (non-condensing) |
| Housing Front (W × H) | 335 × 275 mm |
| Mounting Cut-Out (W × H) | 310 × 248 mm |
| Device Depth (excl. front panel) | 72 mm |
| Weight | ~3.8 kg |
| Configuration Software | WinCC flexible 2007 / 2008 SP2+ (TIA Portal indirect; requires migration) |
| Certifications | CE, cULus, FM Class I Div. 2, C-Tick |
| Lifecycle Status | Blocked for new delivery (01.01.2015), spare-part only; succeeded by TP1200 Comfort |
Main Features and Advantages
Dual Ethernet with native PROFINET IO — the MP 377’s defining leap over MP 370.
The 6AV6644-0AA01-2AX0 carries two RJ45 Industrial Ethernet ports that can operate concurrently: one ties to a S7-1200/1500 PROFINET controller at 100 Mbps while the second lands on a plant-wide TCP/IP or EtherNet/IP segment for SCADA uplink, Sm@rtServer remote viewer, or printer. This dual-homing eliminates the PCI-CP1613/CP343 workaround that MP 370 users endured. For mixed-vendor cells, the MPU also speaks EtherNet/IP and Modbus TCP on the same RJ45 pair, so an Allen-Bradley CompactLogix or a Modbus-TCP power-meter can sit on the same cable plant as the S7-400 — a flexibility the MP 370 12″ simply lacked.
65,536-color TFT and responsive resistive touch in a proven cut-out.
Where MP 370 topped out at 256 colors, the 6AV6644-0AA01-2AX0 renders 16-bit color, making gradient-filled process graphics, photo-realistic machine mockups, and color-coded alarm states visibly cleaner on a 12.1″ SVGA canvas. The 4-wire analog-resistive digitizer tolerates gloved operation and survives the industrial key-press cycle count typical of polyester-faced overlays. Critically, the cut-out (310 × 248 mm) is mechanically compatible with MP 370 12″ Touch and MP 277 10″ Touch apertures, so a 6AV6644-0AA01-2AX0 drops into a cabinet door originally machined for its predecessor without re-cutting — only the 72 mm rear depth (vs. MP370’s ~85 mm) needs verification, and in practice the MP377 is shallower, which relieves rear clearance.
24 MB effective memory + dual removable-storage slots.
12,288 KB base plus 12,288 KB option gives 24 MB of Flash/RAM for screens, alarms (2000+ each), recipes, and trend archives — double the MP 370’s footprint. The CF card slot and MMC/SD slot (≤128 MB) allow bulk archival of batch logs, alarm CSVs, and project clones without a PC. For validated pharma skids, this means the 6AV6644-0AA01-2AX0 can dump a 30-day batch-alarm set to CF at shift change, then the QA clerk pulls the card — no network share, no audit trail gap.
Broad multi-vendor driver set and Sm@rtServer.
Beyond Siemens S7, the panel’s WinCE 5.0 runtime includes drivers for S5, TI 505, WinAC, SINUMERIK, SIMOTION, Allen-Bradley (DF1 & DF485), Mitsubishi FX, Omron (LINK/Multilink), and Modicon Modbus. Sm@rtServer (license-activatable) pushes the 6AV6644-0AA01-2AX0 screen to a remote PC or tablet over the plant LAN, useful for centralized supervision of scattered machines without a full SCADA layer.
Engineering continuity where TIA migration is a non-starter.
Plants sitting on WinCC flexible 2008 projects — especially validated pharma/food lines — often reject a forced move to TIA Portal/WinCC Unified because every screen object, alarm class, and recipe mapping would need rework and re-validation. The 6AV6644-0AA01-2AX0 keeps the .hmi file alive: open, verify tags, download over Ethernet or CF, done. Even S7-1200/1500 can be reached natively over PROFINET, so the PLC side can modernize while the HMI stays on the proven runtime.







Reviews